UPS output power rating (0,9 p.f.) | |||||||
kVA | 8 | 10 | 12 | 15 | 20 | 30 | 40 |
kW | 7,2 | 9 | 10,8 | 13,5 | 18 | 27 | 36 |
General | |||||||
Efficiency in double conversion mode (full load) | 92% | 93% | |||||
Efficiency in double conversion mode (half load) | 90% | 91% | |||||
Distributed paralleling with Hot Sync technology | 4 | ||||||
Field upgradeable | yes | ||||||
Inverter/rectifier topology | transformer-free IGBT with PWM | ||||||
Audible noise | < 50 dB | ||||||
Colour | RAL 7035 | ||||||
Input | |||||||
Nominal voltage rating (configurable) | 220/380, 230/400, 240/415 V 50/60 Hz | ||||||
With external transformer | e.g. 230, 400, 440, 480, 690 V | ||||||
With internal transformer | e.g. 230, 400, 440, 480, 690 V | ||||||
Input voltage range | Low -20% at 100% load/-50% at 50% load without battery discharge; High +10%/max +20% | ||||||
Input frequency range | 45-65 Hz | ||||||
Input power factor | 0,99 | ||||||
Input ITHD | less than 4,5% | ||||||
Soft start capability | Yes | ||||||
Internal backfeed protection | Yes | ||||||
Output | |||||||
Nominal voltage rating (configurable) | 220/380, 230/400, 240/415 V 50/60 Hz | ||||||
With internal transformer | e.g. 230, 440, 480, 690 V | ||||||
Output UTHD | <3% (100% linear load); <5% (reference non linear load) | ||||||
Output power factor | 0,9 (e.g. 9 kW at 10 kVA) | 0,9 (e.g. 27 kW at 30 kVA) | |||||
Permitted load power factor | 0,7 lagging - 0,8 leading | ||||||
Battery | |||||||
Type | Maintenance-free VRLA batteries, NiCd | ||||||
Charging method | ABM technology or Float | ||||||
Temperature compensation | Optional | ||||||
Battery nominal voltage (lead-acid) | 384 V (32x12 V, 192 cells) | 432 V (36x12 V, 216 cells) | |||||
Charging current / Model | Default 3 A *Max 30 A | Default 3 A *Max 60 A | |||||
*May be limited by maximum UPS input current rating | |||||||
Accessories | |||||||
Isolation transformer, long-life batteries, external battery cabinets, UPS Center (input, bypass, distribution), X-Slot connectivity (Web/SNMP, ModBus/ Jbus, Relay, Hot Sync, ViewUPS-X remote display), Hot Sync parallel tie cabinet, integrated manual bypass, external maintenance bypass switch | Isolation transformer, long-life batteries, external battery cabinets, X-Slot connectivity (Web/SNMP, ModBus/ Jbus, Relay, Hot Sync, ViewUPS-X remote display), Hot Sync parallel tie cabinet, integrated manual bypass, external maintenance bypass switch | ||||||
Communications | |||||||
X-Slot | 2 communication bays | ||||||
Serial ports | 1 available | ||||||
Relay inputs/outputs | 2/1 programmable | ||||||
Compliance with standards | |||||||
Safety (CB certified) | IEC 62040-1, IEC 60950-1 | ||||||
EMC | IEC 62040-2, IEC 60945 | ||||||
Performance | IEC 62040-3 | ||||||
Approvals | CE, DNV Type Approval, BV Type Approval and ABS PDA up to 15kVA | ||||||
Other classification survey reports | On request |
In the interests of continuous product improvement all specifications are subject to change without notice.